SECTION 1. General A. Any required means of egress shall not be obstructed or otherwise rendered inoperative. At no time shall any object be placed in front of an exit sign, exit path or exit door that would hamper the identification of or the access of such device. B. Means of egress continuity.
The path of egress travel along a means of
egress shall not be interrupted by any building element other than a
means of egress component as specified in this chapter. Obstructions
shall not be placed in the required width of a means of egress except
projections permitted by this chapter. The required capacity of a means
of egress system shall not be diminished along the path of egress
travel. SECTION 2. Locks and Latches A. All Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
B. Each door
in a means of egress from an occupancy of Group A or E having an
occupant load of 100 or more and any occupancy of Group H-1, H-2, H-3 or
H-5 shall comply with the applicable rules of the FPBSC and shall not be
provided with a latch or lock unless it is panic hardware or fire exit
hardware. SECTION 3. Occupant Load
SECTION 4. EXIT Signs A. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) from the nearest visible exit sign. B Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Exit signs shall be illuminated at all times.
C. To ensure
continued illumination for duration of not less than 60 minutes in case
of primary power loss, the exit signs shall be connected to an emergency
electrical system provided from storage batteries, unit equipment or an
on-site generator. SECTION 5. Egress Illumination
|
©1997-2010 White River Township Fire Department, Inc. - All rights reserved White River Township Fire Department maintains this site ("the Site") for your personal entertainment, information, education, and communication. Feel free to browse the Site, but please read the terms and conditions before doing so. |